IEC 61850 - NODE CONFIGURATION

Primary Station

The figure shows the window for setting the primary station:

 

Item

Description

Item

Description

IP

IED IP Address (0.0.0.0)

Port

Communication port number with the IED. (Standard: 102)

Connection timeout (ms)

Maximum time in milliseconds to establish a TCP/IP connection with the IED.

Connection password

Password that will be used to authenticate the connection to the IED.

Reading mode

Polling/Report - Enables polling and report read requests.



Polling - Enables polling requests.



Report - Enables read requests per report.

Analog read polling rate (ms)

Time period in milliseconds for analog -type (AI) point reading requests. Value zero (0) disables this reading.

Digital read polling rate (ms)

Time period in milliseconds for digital type point (BI) read requests. Value zero (0) disables this reading.

Datasets read polling rate (ms)

Time period in milliseconds for read requests for all DataSet points (DS, DS1, DS2, DS3, DS4). Value zero (0) disables this reading.

Dataset T1 read polling rate (ms)

Time period in milliseconds for read requests for DataSet (DS1) points. Value zero (0) disables this reading.

Dataset T2 read polling rate (ms)

Time period in milliseconds for read requests for DataSet (DS2) points. Value zero (0) disables this reading.

Dataset T3 read polling rate (ms)

Time period in milliseconds for read requests for DataSet (DS3) points. Value zero (0) disables this reading.

Dataset T4 read polling rate (ms)

Time period in milliseconds for read requests for DataSet (DS4) points. Value zero (0) disables this reading.

Report enable polling rate (ms)

Time period in milliseconds to verify that report points are enabled. Verification is done by reading the attribute value Rptena of each reporting point. Zero value (0) disables this cyclic scan, and the system will only attempt to activate and subscribe to Reports once during startup.

Communication status tag

Enter the name of a previously created integer type TAG.
0 = Offline Communication
1 = Online Communication

Last command error tag

Name of the Integer type TAG.
The errors come accompanied by codes and they can be consulted in the session 7.2.1

SCL file name to config points

SCL file name, which will be used for reading points by the browser in the points configuration. The search directory of the files is: C:\Action.NET\Projects|

Quality changes timestamp

Enabled - Enables date/time update when only the quality of the point changes.

Disabled - Disables date/time update when only the quality of the point changes.

Ignore polling on points updated by reports

Enabled - Report points enabled will have the request to read by polling ignored. There is a performance gain in this case, but a loss in the integrity of the data read.

Disabled - Report points enabled will have the request to read by polling. There is a loss of performance in this case, but a gain in the integrity of the data read.

COMTRADE files reading Mode

Download - In this mode of operation, the driver will transfer the COMTRADE files to the computer.

Download/Delete - In this mode of operation, the driver will transfer the COMTRADE files to the computer and delete them from the IED after the transfer is successfully completed.

COMTRADE files download folder

Directory where the transferred COMTRADE files will be saved.

COMTRADE files download polling rate (ms)

Time period in milliseconds for read requests for COMTRADE files. Value zero (0) disables this reading.

FTP username

User with permission to read COMTRADE files by FTP protocol.
If this field is filled. The reading of the files will be done by FTP, otherwise it will be done by MMS.

FTP password

User password with permission to read COMTRADE files by FTP protocol.

Connection AP-Title

AP Title to be used on the connection

Connection AE Qualifier

AE Qualifier to be used for connection

Command Interlock chek

Enabled- will be done the interlock check in the command. Disable- This check will not be made

Command synchro check

Enabled- timing will be performed in the command. Disable- This check will not be made

Secondary Station (Backup Station)