IEC 61850 - NODE CONFIGURATION
Primary Station
The figure shows the window for setting the primary station:
Â
Item | Description |
---|---|
IP | IED IP Address (0.0.0.0) |
Port | Communication port number with the IED. (Standard: 102) |
Connection timeout (ms) | Maximum time in milliseconds to establish a TCP/IP connection with the IED. |
Connection password | Password that will be used to authenticate the connection to the IED. |
Reading mode | Polling/Report - Enables polling and report read requests. |
Polling - Enables polling requests. | |
Report - Enables read requests per report. | |
Analog read polling rate (ms) | Time period in milliseconds for analog -type (AI) point reading requests. Value zero (0) disables this reading. |
Digital read polling rate (ms) | Time period in milliseconds for digital type point (BI) read requests. Value zero (0) disables this reading. |
Datasets read polling rate (ms) | Time period in milliseconds for read requests for all DataSet points (DS, DS1, DS2, DS3, DS4). Value zero (0) disables this reading. |
Dataset T1 read polling rate (ms) | Time period in milliseconds for read requests for DataSet (DS1) points. Value zero (0) disables this reading. |
Dataset T2 read polling rate (ms) | Time period in milliseconds for read requests for DataSet (DS2) points. Value zero (0) disables this reading. |
Dataset T3 read polling rate (ms) | Time period in milliseconds for read requests for DataSet (DS3) points. Value zero (0) disables this reading. |
Dataset T4 read polling rate (ms) | Time period in milliseconds for read requests for DataSet (DS4) points. Value zero (0) disables this reading. |
Report enable polling rate (ms) | Time period in milliseconds to verify that report points are enabled. Verification is done by reading the attribute value Rptena of each reporting point. Zero value (0) disables this cyclic scan, and the system will only attempt to activate and subscribe to Reports once during startup. |
Communication status tag | Enter the name of a previously created integer type TAG. |
Last command error tag | Name of the Integer type TAG. |
SCL file name to config points | SCL file name, which will be used for reading points by the browser in the points configuration. The search directory of the files is: C:\Action.NET\Projects| |
Quality changes timestamp | Enabled - Enables date/time update when only the quality of the point changes. Disabled - Disables date/time update when only the quality of the point changes. |
Ignore polling on points updated by reports | Enabled - Report points enabled will have the request to read by polling ignored. There is a performance gain in this case, but a loss in the integrity of the data read. Disabled - Report points enabled will have the request to read by polling. There is a loss of performance in this case, but a gain in the integrity of the data read. |
COMTRADE files reading Mode | Download - In this mode of operation, the driver will transfer the COMTRADE files to the computer. Download/Delete - In this mode of operation, the driver will transfer the COMTRADE files to the computer and delete them from the IED after the transfer is successfully completed. |
COMTRADE files download folder | Directory where the transferred COMTRADE files will be saved. |
COMTRADE files download polling rate (ms) | Time period in milliseconds for read requests for COMTRADE files. Value zero (0) disables this reading. |
FTP username | User with permission to read COMTRADE files by FTP protocol. |
FTP password | User password with permission to read COMTRADE files by FTP protocol. |
Connection AP-Title | AP Title to be used on the connection |
Connection AE Qualifier | AE Qualifier to be used for connection |
Command Interlock chek | Enabled- will be done the interlock check in the command. Disable- This check will not be made |
Command synchro check | Enabled- timing will be performed in the command. Disable- This check will not be made |
Secondary Station (Backup Station)
The same settings made for the primary station can be made for a secondary station, if any in the installation.
On this page: